Construction Concerns: Firewall Penetrations

By Gregory Havel

Fire-rated partitions and floor-ceiling assemblies as described in National Fire Protection Association (NFPA) 101,Life Safety Code,and in the NFPA and International Code Council building and fire codes are used to separate hazards and areas of buildings from each other. In schools and health care facilities, they separate classrooms,patientrooms, and treatment rooms from each other and from corridors and stairways. In multifamily residential buildings, they separate individual apartments from each other and from corridors and stairways (the means of egress).

In anybuilding, fire-rated partitions must be penetrated by pipes, electrical conduits, cables, and other utilities so that the building can function. Each of these penetrations must be protected so that the fire rating of the floor-ceiling assembly or wall will not be compromised.

Photo 1 shows a pipe penetrating a fire-ratedmasonrywall that was exposed during a remodeling project. On this side of the wall, a rated fire caulk has been installed over backing material, sealing the space between the pipe and the masonry.

(1) Photos by author.

Photo 2 shows the other side of one of the many firewalls in this building. Even though one side of thewallmay be protected properly at each penetration with backing material and fire caulk, the other side of the wall is unprotected. There was no attempt to seal the space between the pipes and the masonry, concrete, or gypsum board drywall on both sides of the wall.

(2)

Penetrations of firewalls are usually inspected by the building officials; fire inspectors are often not in the building until it is ready to be issued an occupancy permit, at which time the penetrations are often concealed above suspendedceilings.

ClickHEREto view a copy of two pages from the Underwriters Laboratories (UL) On-Line Certifications Directory, System Number W-J-1007, a through-penetration firestop system for a single pipe four inches in diameter or smaller that passes through a concrete or masonry wall. Please note that this and most other systems require backing material and fire caulk on both sides of the wall, as they were designed and tested by UL (or another independent testing lab).

A firestop system that is installed on only one side of the wall will not perform as it was designed and tested; it will likely fail early in its fire exposure. This can compromise the safety of building occupants who depend on the corridors and stairways toexit建筑和消防队员s who depend on the same corridors and stairways for rescue and access to fight the fire and for their emergency evacuation routes.

Firefighters and fire inspectors must become familiar with firestop methods and materials, tour buildings underconstructionand remodeling to observe the installation of firestop materials and to develop a working relationship with their municipal building department so that deficiencies and omissions can be communicated and corrected.

Download this article as a PDFHERE

Gregory Havel属于伯灵顿镇(WI)火德partment; retired deputy chief and training officer; and a 35-year veteran of the fire service. He is a Wisconsin-certified fire instructor II, fire officer II, and fire inspector; an adjunct instructor in fire service programs at Gateway Technical College; and safety director for Scherrer Construction Co., Inc. Havel has a bachelor’s degree from St. Norbert College; has more than 35 years of experience in facilities management and building construction; and has presented classes at FDIC.